Features of the TLV12450B - 12V 4.5Ah Sealed Lead Acid Battery with F2 Terminals
• Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance or water adding
• Not restricted for air transport-complies with IATA/ICAO Special Provision A67
• UL-recognized component
• Can be mounted in any orientation
• Computer designed lead, calcium tin alloy grid for high power density
• Long service life in float or cyclic applications
• Maintenance-free operation
• Low self discharge
Applications
• UPS Standby Power Applications
• Data Centers
• Emergency 911 Centers
• Hospitals & Medical Applications
• Military Power Equipment
• Emergency Lighting
• Fire Detection and Alarm Devices
Product Specifications
Dimensions
Terminal Type: F2
Length (mm/inch): 140 / 5.49
Width (mm/inch): 38 / 1.50
Height (mm/inch): 94 / 3.70
Total Height (mm/inch): 100 / 3.94
Approx. Weight (kg/lbs): 1.25 / 2.75
Nominal Voltage:
Capacity:
20HR (10.5V): 4.5Ah
10HR (10.5V): 3.9Ah
1HR (9.60V): 2.73Ah
Internal Resistance (Fully Charged, 25°C):
Approx. 38mΩ
Capacity Affected by Temperature (20HR):
40°C: 102%
25°C: 100%
0°C: 85%
-15°C: 65%
Self-Discharge (25°C):
3 month: Remaining Capacity: 91%
6 month: Remaining Capacity: 82%
12 month: Remaining Capacity: 65%
Nominal Operating Temperature:
25°C ± 3°C (77°F ± 5°F)
Operating Temperature Range:
Discharge: -15°C ~ 50°C (5°F ~ 122°F)
Charge: -10°C ~ 50°C (14°F ~ 122°F)
Charge: -20°C ~ 50°C (-4°F ~ 122°F)
Float Charging Voltage (25°C):
13.60 to 13.80V Temperature Compensation: -18mV/°C
Cyclic Charging Voltage (25°C):
14.50 to 14.90V Temperature Compensation: -30mV/°C
Maximum Charging Current: 1.35A
Maximum Discharge Current: 45A (5 sec)
Designed Floating Life (20°C): 10 years
Terminal Material: Copper
Constant Current Discharge Characteristics
Constant Power Discharge Characteristics
(Note) The above characteristics data are average values obtained within three charge/discharge cycles not the mimimum values.